Air handling units, duct systems, filter banks and pressurised rooms in Pakistani hospitals, pharma plants, data centres, textile mills and commercial buildings all depend on one small number: differential pressure, usually in inches of water column (in WC) or pascals. A falling duct static points to a slipping fan belt or an open damper. A rising filter ΔP means the filter is loading. A lost room cascade means air is moving the wrong way. A local gauge shows the number to someone standing in front of it. A transmitter sends it to the BMS, PLC or SCADA, where it can drive a VFD, trigger an alarm and be trended.
This note looks at the ACI DLP differential low pressure transmitter. Figures come from the ACI DLP datasheet hosted on our product page and from the current Tetracon product pages. Where we give general engineering advice it is labelled as general. Nothing here goes beyond the manufacturer's published data. Tetracon (Pvt.) Ltd. is the sole authorized agent for ACI (Automation Components, Inc.) in Pakistan.
Why a field-selectable DP transmitter?
- One model, several spans. Each DLP has up to 8 field-selectable ranges, unidirectional or bidirectional. The A/DLP-001 covers 0–0.1, 0.2, 0.5 or 1 in WC (and ± the same), the A/DLP-010 covers 0–1, 2, 5 or 10 in WC and the A/DLP-040 covers 0–10, 20, 30 or 40 in WC (datasheet).
- One model, three outputs. Outputs are field selectable: 4–20 mA two-wire loop powered (the default), or 0–5 / 0–10 VDC three-wire (datasheet). The same spare suits a 4–20 mA PLC card or a 0–10 V BMS controller input.
- Accuracy to match HVAC duties. ±0.50 % FSO, including linearity, hysteresis and repeatability at 21.5 °C, with a thermal effect of ±0.12 % FSO/°C relative to 21.5 °C (datasheet).
- Quick to commission. A hinged cover with a locking tab gives access to the pushbutton zero and the range and output selectors. An optional five-digit LCD shows the reading during installation and checks (datasheet).
- Long warranty. The DLP Series is covered by ACI's five-year limited warranty (datasheet).
How the DLP works
The DLP uses a piezoresistive silicon sensing element. The high and low pressure ports connect to the two sides of the sensor, and the electronics turn the differential pressure into an analog output scaled to the selected range. Response time (0–100 % FSO) is 4 seconds and the output updates every 0.5 seconds (datasheet). In bidirectional mode the output covers both positive and negative pressure, which suits room-to-corridor cascades that can reverse when doors open (datasheet; general).
The DLP is for non-corrosive, non-ionic gases such as air and other dry gases (datasheet). It is not a liquid or wet-steam transmitter. Ports are nickel-plated brass or stainless steel and accept 1/4″ O.D. × 0.170″ I.D. poly tubing. An optional 7″ aluminium duct-static pitot tube (A/PT-DLP, 6.75″ insertion) and a 35 mm DIN rail clip (A/DRC-DLP) are available (datasheet).
ACI DLP at a glance
| Item | From the datasheet |
|---|---|
| Sensing element | Piezoresistive silicon, differential |
| Ranges (field selectable, uni or bidirectional) | A/DLP-001: 0.1 / 0.2 / 0.5 / 1 in WC; A/DLP-010: 1 / 2 / 5 / 10 in WC; A/DLP-040: 10 / 20 / 30 / 40 in WC |
| Accuracy | ±0.50 % FSO (linearity, hysteresis and repeatability at 21.5 °C) |
| Thermal effect | ±0.067 % FSO/°F (0.12 % FSO/°C), relative to 21.5 °C |
| Response / update | 4 s (0–100 % FSO); output update every 0.5 s |
| Outputs | 4–20 mA two-wire loop powered (default, limited to 21.5 mA); 0–5 / 0–10 VDC three-wire (limited at 5.25 / 10.5 VDC) |
| Supply | 4–20 mA: 16–36 VDC (250 Ω max) or 22–36 VDC (500 Ω max), or 24 VAC ±10 %; 0–5/0–10 V: 15–36 VDC (>5 kΩ load) or 24 VAC ±10 % |
| Proof / burst | DLP-001: 270 / 415 in WC; DLP-010: 350 / 550 in WC; DLP-040: 562 / 1004.7 in WC |
| Temperature | Operating −20 to 85 °C; compensated 0 to 50 °C; storage −30 to 85 °C; 10–95 % RH non-condensing |
| Media | Non-corrosive, non-ionic gases such as air and other dry gases |
| Enclosure / wiring | Flame-retardant polycarbonate, UL94-5VA; spring terminal blocks, 16–24 AWG; watertight cordgrip (1/2″ NPT when removed) |
| Options | Five-digit LCD; pitot tube; DIN rail clip |
| Approvals / weight | CE, REACH, RoHS2, WEEE; 0.240 kg (no LCD) or 0.263 kg (LCD) |
Picking the model and range
For reference, 1 in WC is about 249 Pa, so 0.1 in WC is about 25 Pa, 10 in WC is about 2.49 kPa and 40 in WC is about 9.96 kPa (unit conversion). Typical choices (general HVAC practice; confirm against your design pressures):
- Room cascades and pressurised rooms (A/DLP-001). Room-to-room differentials are usually a few pascals to a few tens of pascals, so the 0.1, 0.2 or 0.5 in WC bidirectional ranges fit (general).
- Duct static and filter ΔP (A/DLP-010). Supply duct static set points and filter bank differentials typically sit within 1–10 in WC (general).
- Higher fan and process differentials (A/DLP-040). Fan inlet-to-outlet, dust collector and process air duties up to 40 in WC (general).
- Use the tightest range that covers the duty. Accuracy is a percentage of full-scale output, so a span close to the working pressure gives the best absolute figure (datasheet basis; general).
- Check the overpressure. Proof pressure is 270, 350 or 562 in WC depending on the model, well above the span, but keep the ports away from compressed-air test lines (datasheet; general).
Where it fits in Pakistan
- Building and duct static pressure. ACI lists building and duct static pressure first. A duct static signal lets the BMS control supply fan VFDs in VAV systems (datasheet; general).
- Filter monitoring. A DP across each AHU filter stage tells maintenance when to change filters, instead of a fixed calendar (datasheet; general).
- Air flow measurement. With a pitot tube or flow station, the DP signal becomes a velocity and flow reading for fresh-air and exhaust checks (datasheet; general).
- Pharma, hospital and cleanroom cascades. Bidirectional low ranges suit corridor-to-room and isolation room checks. See our differential pressure monitoring note for the wider programme (general).
- Process control. ACI also lists process control, for example dry-gas blower and burner air differentials (datasheet; general).
- Pakistan climate. The DLP operates from −20 to 85 °C but is temperature compensated from 0 to 50 °C. Rooftop AHUs in Sindh and Punjab summers can exceed that, so mount it in the plant room or a shaded enclosure where possible (datasheet; general for Pakistan).
Practical notes for a reliable installation
- Mount and zero. Mount the transmitter, leave both ports open to the same pressure and press the zero button before connecting tubes (datasheet: pushbutton zero; general).
- Tubing. Use 1/4″ O.D. × 0.170″ I.D. poly tubing, keep runs short, avoid kinks and route tubes so condensate cannot collect in them (datasheet; general).
- Wiring. For 4–20 mA two-wire, size the supply for the loop: 16–36 VDC up to 250 Ω or 22–36 VDC up to 500 Ω. Voltage outputs need three wires and a load above 5 kΩ (datasheet).
- Dry air only. The sensor is rated for non-corrosive, non-ionic dry gases. Do not use it on wet, corrosive or solvent-laden streams (datasheet).
- Pair with a local gauge. A local dial gauge such as the Miljoco LP2507L low pressure gauge gives operators a reading at the door or filter even if the BMS is down (general). Our LP2507L note covers gauge selection.
Related products and when to choose them
| Duty | Product | Key figure (datasheet / product page) |
|---|---|---|
| Wired DP to BMS / PLC for duct static, filters, air flow | ACI DLP | 0.1–40 in WC spans; ±0.50 % FSO; 4–20 mA or 0–10 V |
| Wireless, cloud-logged cleanroom or isolation room DP | SensoScientific Wi-Fi DP sensor | ±0.25 in WC (DP001 probe); ±0.002 in WC |
| Local dial indication at a door or filter | Miljoco LP2507L | 2½″ diaphragm gauge; up to 10 psi; ±1.5 % FS |
| CO and NO2 for car parks and plant rooms | ACI Q6/B6 | Dual-sensor BACnet/Modbus gas sensor |
| Energy sub-metering on the same BMS | ACI KW350 | Bi-directional power meter, BACnet/Modbus |
For more ACI building sensors see our car park CO / NO2 note and the KW350 energy sub-metering note. The wider range is on the Humidity & Pressure category page and the ACI manufacturer page.
What to send with an enquiry
- Duty (duct static, filter ΔP, room cascade, air flow or process) and the expected pressure, including whether it can reverse.
- Required span in in WC or Pa, so we can match the A/DLP-001, -010 or -040.
- Output (4–20 mA, 0–5 V or 0–10 V) and the available supply (VDC or 24 VAC).
- Whether you need the LCD, a pitot tube or a DIN rail clip.
- Mounting location and ambient temperature, especially for rooftop AHUs.
- Quantity, BMS or PLC make, and any local gauges or wireless monitoring needed alongside.
FAQ
What ranges does the ACI DLP cover?
From 0–0.1 in WC up to 0–40 in WC across three models. The A/DLP-001 selects 0.1, 0.2, 0.5 or 1 in WC, the A/DLP-010 selects 1, 2, 5 or 10 in WC and the A/DLP-040 selects 10, 20, 30 or 40 in WC, each unidirectional or bidirectional.
How accurate and fast is it?
The datasheet gives ±0.50 % FSO, including linearity, hysteresis and repeatability at 21.5 °C, with a thermal effect of ±0.12 % FSO/°C. Response time is 4 seconds for 0–100 % FSO and the output updates every 0.5 seconds.
Which outputs and supplies does it accept?
4–20 mA two-wire loop powered is the default (16–36 VDC up to 250 Ω or 22–36 VDC up to 500 Ω, or 24 VAC). The 0–5 VDC and 0–10 VDC outputs are three-wire, from 15–36 VDC or 24 VAC into a load above 5 kΩ.
Can it measure liquids or corrosive gases?
No. ACI rates the DLP for non-corrosive, non-ionic gases such as air and other dry gases. For other media, send the application details and we will check with the manufacturer.
When should I choose a wireless sensor or a gauge instead?
Choose the DLP when the reading must go to a BMS or PLC over 4–20 mA or 0–10 V. Choose the SensoScientific Wi-Fi DP sensor where cabling is hard and a cloud-logged, alarmed record is needed. Choose a local gauge such as the Miljoco LP2507L for a simple reading at the point of use, often alongside a transmitter.
Need help selecting a differential pressure transmitter for duct static, filters, air flow or room cascades in Pakistan? Contact Tetracon with the duty, span, output and mounting location. You can also browse the DLP product page and the ACI manufacturer page.