Q6/B6 Series Dual-Sensor BACnet/Modbus Gas Sensor

Dual-channel gas sensor combining CO with a second selectable toxic/combustible gas.

ModelQ6-B6-Series (B6-CO/NO2-10P)
SKUQ6-B6-SERIES
CategoryGas Detection

Key Features

  • Dual-sensor: main CO channel + remote second gas channel
  • B6: BACnet MS/TP (Master/Slave); Q6: Modbus RTU / OptoMux
  • 3 programmable SPDT relays
  • LCD graphic display with backlight (TWA, STEL, concentration)
  • 80 dB buzzer, 3 programmable tones
  • NEMA 4, 4X, 12, 13 / IP66 polycarbonate enclosure
  • De-pluggable screw terminal blocks

Overview

The ACI Q6/B6 Series pairs a main Carbon Monoxide sensor with a remote second sensor channel — NO2, methane, hydrogen, or other toxic/combustible gases — in one BACnet MSTP (B6) or Modbus RTU (Q6) smart sensor. It shares the same rugged NEMA 4X enclosure and 3-relay platform as ACI's single-gas Q5/B5 Series, with an LCD graphic display showing TWA, STEL, and live concentration.

Working Principle

The main channel continuously measures CO while the remote channel monitors a second selected gas (e.g. NO2), with both readings shown on an LCD graphic display (TWA, STEL, concentration). Three programmable SPDT relays and an 80 dB buzzer drive local alarms, and results are available over RS-485 — Modbus RTU/OptoMux for Q6, or BACnet MS/TP (Master/Slave) for B6.

Benefits

  • Monitors two gas hazards from a single device and enclosure
  • Direct BACnet or Modbus integration into building/plant automation
  • Field-replaceable sensor modules simplify long-term maintenance
  • Same rugged platform and mounting as the single-gas Q5/B5 Series

Technical Specifications

Detection
Main ChannelCarbon Monoxide (CO), 0–250 ppm
Remote ChannelSelectable — e.g. NO2 0–10 ppm, methane, hydrogen
Life ExpectancyElectrochemical: 2–3 yrs; Catalytic: 3 yrs; CO: 7 yrs; O2/H2: 18 months
Communications
B6 ProtocolBACnet MS/TP, 9600–76,800 bps (default 38,400)
Q6 ProtocolModbus RTU / OptoMux, 1200–76,800 bps (default 4800)
Outputs
Relays3 × SPDT
DisplayLCD graphic with backlight
Power
Supply24 VDC (+18–30 VDC) or 24 VAC (+15–24 VAC) nominal
Consumption0.3 A max, 8.4 VA
Enclosure
RatingNEMA 4, 4X, 12, 13 / IP66
MaterialPolycarbonate (Lexan), UL94 V-0
EnvironmentIndoor use only
Operating Conditions
Warm-Up24 hours before calibration
Humidity5–95% RH, non-condensing
Operating Pressure14.696 psi ±10%

Downloads

Datasheet (PDF)PDF

Frequently Asked Questions

What warranty is offered on this product?

All Tetracon-supplied instruments carry the original manufacturer warranty (typically 12–24 months) plus first-line local support from our Islamabad service centre.

Do you provide installation and commissioning?

Yes. Our manufacturer-trained engineers offer on-site installation, commissioning and startup training anywhere in Pakistan.

Are spares and calibration available locally?

Common spares are held in local stock. Calibration is available at our lab or on-site with NIST-traceable reference standards.

How long is the typical lead time?

Stocked items ship within 3–5 working days; engineered configurations typically 6–10 weeks depending on manufacturer schedule.

Request a Quote — Q6/B6 Series Dual-Sensor BACnet/Modbus Gas Sensor

Complete the form below and one of our engineers will respond within 1 working day with pricing and lead time. Prefer email? Contact our sales team.