Home About Us Manufacturers Products Services Clients Downloads Blog Guides FAQ Contact
Miljoco P60148LY-SS 6 inch rear flange stainless steel pressure gauge for surface mounting in Pakistan
Miljoco P60148LY-SS surface-mount stainless steel pressure gauge, shown with the P6098LY-SS, P4098LY-SS and P2598LZ-SS (datasheets and product pages).

Not every pressure gauge can simply be screwed onto a pipe stub and left to hang there. On skids, pump stations, filter housings, compressor and chiller panels and walls next to a process line, operators need the dial fixed to a surface at eye level, with the process connection running to it by tubing (general). A gauge that hangs off its own thread in those places vibrates, gets knocked and is often read from an angle (general).

This note looks at the Miljoco P60148LY-SS, a 6-inch industrial pressure gauge with a stainless steel rear flange case for surface mounting and 316 stainless steel wetted parts, together with its stem-mounted sister models, the 6-inch P6098LY-SS, the 4-inch P4098LY-SS and the compact 2½-inch P2598LZ-SS. It covers what the datasheets say, how to order the right range and fill, and how to install the gauges in Pakistani plants. Figures come from the Miljoco datasheets hosted on our product pages and the current Tetracon product pages. General engineering advice is labelled as general, and nothing here goes beyond the published data. Tetracon (Pvt.) Ltd. is the sole authorized agent for Miljoco Corporation in Pakistan.

Why a surface-mount stainless gauge

  • Made to be surface mounted. Miljoco describes the P60148LY-SS and PLF60148LY-SS as gauges for applications where the gauge must be surface mounted, with a stainless steel rear flange case (datasheet).
  • Stainless where the fluid touches it. The tube and socket are 316 stainless steel and the movement is stainless steel (datasheet), which suits process fluids, wash-down areas and outdoor sites where brass internals would not last (general).
  • Grade 1A accuracy on a 6-inch dial. The gauge is calibrated to ±1 % of full scale, ASME B40.100 Grade 1A (datasheet), and a 6-inch dial is easier to read from a walkway than a 2½-inch or 4-inch dial (general).
  • Dry or liquid filled. The case can be filled with glycerine or silicone to prolong the life of the internal mechanism when it is exposed to vibration, and the datasheet marks the gauge as field liquid-fillable (datasheet).
  • Vacuum to 5000 psi. Standard ranges run from 30 inHg vacuum (-100 kPa) through compound ranges up to 0–5000 psi / 0–35,000 kPa (datasheet).

P60148LY-SS at a glance

ItemMiljoco P60148LY-SS (datasheet)
Dial size6 inch; aluminium dial, white finish with black markings
MountingStainless steel rear flange case for surface mounting
Accuracy±1 % of full scale (ASME B40.100 Grade 1A)
Case and ring300 series stainless steel; bayonet-type ring with gasket
LensPolycarbonate
PointerAluminium, black, micro-adjustable
MovementStainless steel, rotary type
Tube and socket (wetted parts)316 stainless steel
Connection1/4" NPT bottom outlet
Process temperatureDry P60148LY-SS: -40 to 120 °C (-40 to 250 °F); glycerine-filled PLF60148LY-SS: -18 to 60 °C (0 to 140 °F)
Ambient temperatureDry: -40 to 60 °C (-40 to 140 °F); glycerine-filled: -18 to 60 °C (0 to 140 °F)
Fill optionsDry (P60148LY-SS), glycerine (PLF60148LY-SS) or silicone (PSF60148LY-SS)
Standard ranges30 inHg-0 (-100-0 kPa); compound 30 inHg-0-15 psi up to 30 inHg-0-300 psi (-100 to 2000 kPa); pressure 0-15 psi (0-100 kPa) up to 0-5000 psi (0-35,000 kPa)
Steam serviceA coil syphon must be installed on the connection

To order, Miljoco lists the model number (P60148LY), the range code (for example 08 for 0–300 psi / 0–2000 kPa) and SS for stainless internals; specify PLF60148LY-SS for glycerine fill or PSF60148LY-SS for silicone fill (datasheet).

Miljoco P60148LY-SS 6 inch rear flange stainless steel pressure gauge with key datasheet figures
Miljoco P60148LY-SS: 6-inch dial, rear flange case for surface mounting, 316 SS tube and socket, ±1 % FS Grade 1A, dry or liquid filled (datasheet figures).
Comparison of Miljoco P60148LY-SS, P6098LY-SS, P4098LY-SS and P2598LZ-SS stainless steel gauges from the datasheets
Choosing a Miljoco stainless steel industrial gauge: P60148LY-SS versus P6098LY-SS, P4098LY-SS and P2598LZ-SS (datasheets).

Rear flange, 6-inch, 4-inch or 2½-inch

  • P60148LY-SS: 6-inch dial, stainless steel rear flange case for surface mounting, ±1 % FS Grade 1A, polycarbonate lens, micro-adjustable pointer, dry, glycerine or silicone fill (datasheet). The choice for walls, skids, frames and panels where the gauge must be fixed to a surface (general).
  • P6098LY-SS: the same 6-inch Grade 1A specification, 316 SS tube and socket, polycarbonate lens and fill options, in a stainless steel case for direct mounting on the 1/4" NPT bottom connection (datasheet). Use it where the gauge can sit on the line itself (general).
  • P4098LY-SS: 4-inch dial with the same ±1 % FS Grade 1A accuracy and 316 SS wetted parts, acrylic lens, with a glass lens version (P4099LY-SS), glycerine and silicone fills and a 1/2" NPT connection (P4098LY-SS-50) listed as options (datasheet). A good fit for tighter spaces that still need Grade 1A (general).
  • P2598LZ-SS: compact 2½-inch gauge with 316 SS tube and socket and a 300 series stainless case, calibrated to ±1.6 % FS (exceeds ASME B40.100 Grade B), non-adjustable pointer, dry or glycerine filled (PLF2598LZ-SS); a back outlet is available on request from the factory (datasheet). For small equipment, local indication and instrument panels (general).

All four datasheets share the same process temperature limits (dry -40 to 120 °C, glycerine-filled -18 to 60 °C) and the same warning that a coil syphon must be fitted for steam service (datasheet).

Choosing range and fill

  • Pick a range with headroom. A common rule is to choose a range so that the normal operating pressure sits around the middle of the dial (general). For example, a line that normally runs at about 100 psi fits the 0–200 psi range code 07 (0–1400 kPa) on the P60148LY-SS (datasheet range; general advice).
  • Use a compound range on suction lines. Pump suction, vacuum-assisted filters and lines that can go below atmospheric need a compound range such as 30 inHg-0-60 psi (-100 to 400 kPa, code 004) (datasheet), so the pointer does not sit on the stop pin during vacuum (general).
  • Check the dual scale. The standard ranges are dual psi and kPa scales, with the figure and division intervals listed in the datasheet (datasheet). Confirm which unit your operators and SOPs use, so the main scale is the one people read (general).
  • Fill against vibration and pulsation. Glycerine (PLF60148LY-SS) or silicone (PSF60148LY-SS) fill prolongs the life of the mechanism under vibration (datasheet). Reciprocating pumps, compressors and diesel gensets are the typical places where a dry gauge pointer flutters and wears out early (general).
  • Mind the filled-gauge temperature limits. The glycerine-filled version is rated 0 to 140 °F (-18 to 60 °C) for both process and ambient, against -40 to 120 °C process for the dry gauge (datasheet). In a hot plant room or on an exposed rooftop in a Pakistani summer, check the case temperature before choosing a filled gauge (general).

Installing it in a Pakistani plant

  • Mount it where it is read. Fix the rear flange to a wall, frame or panel at eye level near the operator's position and run impulse tubing to the 1/4" NPT bottom connection (datasheet connection; general practice).
  • Fit an isolation valve. A gauge valve or needle valve between the process and the gauge allows the gauge to be removed for calibration or replacement without shutting down the line (general).
  • Steam needs a syphon. Miljoco states that a coil syphon must be installed on the connection when the gauge is used on steam (datasheet). The syphon keeps a condensate seal between the live steam and the Bourdon tube (general).
  • Keep the dial upright and visible. Mount the gauge with the dial vertical and out of direct sun where possible; a 6-inch white dial with black markings (datasheet) reads well from a walkway when it faces the operator (general).
  • Zero check. The pointer is micro-adjustable (datasheet), so a zero check with the gauge isolated and vented is a quick routine maintenance task (general).

Where it fits in Pakistan

  • Chemical and process plants. Chemical plants and industrial processing are listed applications on the product page (product page), where 316 SS wetted parts suit corrosive fluids (product page).
  • Panel and surface installations. Panel-mounted installations are listed on the product page (product page), for example on skid frames, filter and pump panels and boiler-house walls (general).
  • Steam service. Steam service with a coil syphon is listed (product page; datasheet), for example boiler headers and steam distribution in textile, food and pharma plants (general).
  • Water, utilities and HVAC. Pump stations, chilled-water plants and fire water systems often need a large dial mounted on a wall or frame next to the pumps (general).
NeedProductKey point
6-inch gauge fixed to a wall, frame or panelMiljoco P60148LY-SSRear flange SS case, 316 SS wetted parts, ±1 % FS Grade 1A (datasheet)
6-inch gauge on the lineMiljoco P6098LY-SSSame Grade 1A specification, bottom connection (datasheet)
4-inch stainless gaugeMiljoco P4098LY-SS±1 % FS Grade 1A, glass lens and 1/2" NPT options (datasheet)
Compact stainless gaugeMiljoco P2598LZ-SS2½-inch, ±1.6 % FS, dry or glycerine filled (datasheet)

For a wider view of gauge selection, read our industrial pressure gauge selection note, and for draft and low-pressure work our Miljoco LP2507L note. The wider range is on the Process Instrumentation category page, our selection guides and the Miljoco Corporation manufacturer page.

What to send with an enquiry

  • The process fluid, its normal and maximum pressure, and whether the line can go into vacuum.
  • The process and ambient temperature at the gauge, and whether it is on steam service.
  • How the gauge will be mounted (surface or wall, on the line, or in a panel) and the dial size you need.
  • Whether there is vibration or pulsation (pumps, compressors, engines), so we can advise on a glycerine or silicone fill.
  • The dial unit your operators use (psi, kPa or bar) and the quantity.

Send these to Tetracon and our engineers will confirm the right model, range code and lead time. Our services team in Islamabad supports installation and calibration across Pakistan.

FAQ

What is the Miljoco P60148LY-SS?

It is a 6-inch industrial pressure gauge with a 300 series stainless steel rear flange case for surface mounting, 316 stainless steel tube and socket, and ±1 % full-scale accuracy to ASME B40.100 Grade 1A (datasheet).

What pressure ranges are available?

Standard ranges run from 30 inHg vacuum (-100 kPa), through compound ranges up to 30 inHg-0-300 psi, to pressure ranges from 0-15 psi (0-100 kPa) up to 0-5000 psi (0-35,000 kPa) (datasheet).

Can it be liquid filled?

Yes. Specify PLF60148LY-SS for glycerine fill or PSF60148LY-SS for silicone fill; the datasheet also marks the gauge as field liquid-fillable. The glycerine-filled version is rated 0 to 140 °F (-18 to 60 °C) (datasheet).

Can I use it on steam?

Yes, with a coil syphon. Miljoco states that a coil syphon must be installed on the connection when the gauge is used on steam applications (datasheet).

Who supplies Miljoco gauges in Pakistan?

Tetracon (Pvt.) Ltd., Islamabad, is the sole authorized agent for Miljoco Corporation in Pakistan and supplies the Miljoco gauge and thermometer range with local technical support. Contact us with your fluid, pressure and mounting for a quotation.

Specifying pressure gauges for a skid, pump station or process line in Pakistan? Contact Tetracon with the pressure range, fluid and mounting. You can also browse the P60148LY-SS product page and the Miljoco Corporation manufacturer page, or the full product catalogue and all manufacturers.

Talk to a Tetracon engineer All articles