Home About Us Manufacturers Products Services Clients Downloads Blog Guides FAQ Contact
HW Hanwei Electronics Group Corporation

GTQ-WD2200 Fixed Gas Detector

Industrial fixed detector for combustible or toxic gas, with 4–20 mA, HART and RS485, three relays, and a stainless-steel enclosure.

ModelGTQ-WD2200
SKUHW-GTQ-WD2200
CategoryGas Detection

Key Features

  • 4–20 mA analogue output, HART, and RS485-RTU digital communications
  • Three relays for first alarm, second alarm and fault (SPST, 3 A 30 V DC or 3 A 250 V AC)
  • High-performance LCD with LED status indication
  • Non-contact operation by magnetic bar or infrared remote control
  • Smart sensor module, free of calibration and easy to maintain
  • Bluetooth communication, with optional remote upgrade
  • Stainless-steel enclosure, IP66/67, NPT 3/4 cable entry

Overview

The GTQ-WD2200 is a fixed industrial gas detector for combustible or toxic gas. It uses a high-performance sensor and microcontroller, with a clear LCD, a replaceable smart sensor module that needs no field calibration, and non-contact operation by magnetic bar or infrared remote. Analogue, HART and RS485-RTU outputs, together with three relays, allow it to sit on a conventional plant PLC or DCS as well as a HART handheld communicator. Bluetooth is built in, and a remote-upgrade option is available.

Working Principle

The detector samples the atmosphere by natural diffusion. Status is shown on an LCD and by coloured LEDs (green for power, red for alarm, yellow for fault). Outputs include 4–20 mA, HART and RS485-RTU, plus relays for first alarm, second alarm and fault.

Benefits

  • HART and RS485 sit comfortably on existing plant control networks
  • The smart sensor module can be changed without a field calibration set-up
  • Magnetic or infrared control avoids opening the enclosure in a hazardous area

Technical Specifications

Sensing
Measuring gasCombustible gas or toxic gas
Sample methodNatural diffusion
Response timeLEL: T90 ≤ 15 s; toxic gas: T90 ≤ 30 s
Electrical & outputs
PowerDC 24 V ± 6 V, ≤ 3.0 W
Electrical output4–20 mA, HART, RS485-RTU
RelaysFirst alarm, second alarm and fault; SPST contacts rated 3 A 30 V DC or 3 A 250 V AC
OperationMagnetic bar or infrared remote control
State indicationYellow — fault; red — alarm; green — power
Physical & certification
Enclosure materialStainless steel
Ingress protectionIP66/67
Cable entryNPT 3/4
Dimensions & weight130 × 209 × 116 mm, about 2.0 kg
Ex gradeII 2GD Ex db IIC T6 Gb / Ex tb IIIC T80 °C Db, −40 °C ≤ Ta ≤ +60 °C
Operating temperatureLEL: −40 °C to 70 °C; toxic: −20 °C to 50 °C
Humidity≤ 95 %RH (no condensation)
Ambient pressure86 kPa to 106 kPa

Downloads

Product brochure (PDF)PDF

Frequently Asked Questions

What warranty is offered on this product?

All Tetracon-supplied instruments carry the original manufacturer warranty (typically 12–24 months) plus first-line local support from our Islamabad service centre.

Do you provide installation and commissioning?

Yes. Our manufacturer-trained engineers offer on-site installation, commissioning and startup training anywhere in Pakistan.

Are spares and calibration available locally?

Common spares are held in local stock. Calibration is available at our lab or on-site with NIST-traceable reference standards.

How long is the typical lead time?

Stocked items ship within 3–5 working days; engineered configurations typically 6–10 weeks depending on manufacturer schedule.

Request a Quote — GTQ-WD2200 Fixed Gas Detector

Complete the form below and one of our engineers will respond within 1 working day with pricing and lead time. Prefer email? Contact our sales team.